System manual CECX / Bus link module CECX-B-CO
34.3.2 Adding modules
The CECX-B-CO makes 8.5 W available for the supply of up to 12 add-on
modules.
To guarantee stable functioning of the module cluster the power demand
on the added-on modules must not exceed 8.5 W.
Information
For the calculation of the number of modules that can be added, the speci-
fied performance value given in the technical specifications under "Power
consumption 5 V on the K-Bus" must be used.
34.3.3 Accessories
34.3.3.1 Connector strip
Voltage supply: The module uses standard male connectors with grid
dimension 5.08 mm.
Required socket board:
1 block with 2 connections.
CAN connection 9-pole DSUB connector
Female connector Color Number Order no. Weidmüller
2-pole sw 1 BLZF 5.08/2 SN SW - 170769
Information
Larger terminal blocks may be used to group multiple signals. The current
carrying capacity of the terminal block is thus, however, reduced (according
to derating curve of the terminal block manufacturer.)
The technical data for the terminals are contained in the technical data
sheet of the manufacturer of the female connectors.
34.4 CANOpen protocol
34.4.1 Definitions
CAN:
Controller Area Network is an internationally standardized serial Bus sys-
tem.
CECX-II 34-4