6.2.1 INTERMICOM COMMAND BITS
To test the InterMiCOM command bits, go to the INTERMICOM COMMS column and do the following:
1. Enter any test pattern in the Test Pattern cell in the by scrolling through and changing selected bits
between 1 and 0. The entered pattern is transmitted through the loopback.
2. Check that the IM Output Status cell matches the applied Test Pattern.
3. Check that all 8 bits in the IM Input Status cell are zero.
6.2.2 INTERMICOM CHANNEL DIAGNOSTICS
Check that the following cells in the INTERMICOM COMMS column all read OK.
Data CD Status
FrameSync Status
Message Status
Channel Status
6.2.3
SIMULATING A CHANNEL FAILURE
1. Simulate a failure of the communications link by breaking a connection and checking that some of these
cells show Fail.
2. Restore the communications loopback and ensure that the four diagnostic cells display OK.
Note:
Some or all of these cells show Fail depending on the communications configuration and the way the link has failed.