2.3.2 NON-DIRECTIONAL ELEMENTS
Time delayed SEF protection
V
I
R R R Rn
K
cn
CT L p
+ + +
2
2( )
Instantaneous SEF protection
V
I
R R R Rn
K
sn
CT L p
+ + +
2
2( )
2.4 SEF PROTECTION (CORE-BALANCED CT)
2.4.1 DIRECTIONAL ELEMENTS
Instantaneous element
V
I
R R Rn
K
fn
CT L
+ +
2
2( )
Note:
Ensur
e that the phase error of the applied core balance current transformer is less than 90 minutes at 10% of rated current
and less than 150 minutes at 1% of rated current.
2.4.2 NON-DIRECTIONAL ELEMENTS
Time delayed element
V
I
R R Rn
K
cn
CT L
+ +
2
2( )
Instantaneous element
V I R R Rn
K sn CT L
+ +( )2
Note:
Ensur
e that the phase error of the applied core balance current transformer is less than 90 minutes at 10% of rated current
and less than 150 minutes at 1% of rated current.
2.5 LOW IMPEDANCE REF PROTECTION
For X/R < 40 and
f
< 15
n
V I R R
K n CT L
+24 2( )
For 40 < X/R < 120 and 15
n
< If < 40
n
V I R R
K n CT L
+48 2( )
Chapter 9 - Current Transformer Requirements P24xM
196 P24xM-TM-EN-2.1