EasyManua.ls Logo

GE P24DM - Application Notes; StartStall Protection; Figure 78: Automatic Restart Failed- Voltage Restored after the Set Time

GE P24DM
600 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V00793
Stall Setting
Starting Current
Current
0
Due to trip
Time
Time
Start Successful
0
1
t
0
t
1
At the time t1 when the timer is
timed out and the voltage has
remained below Low V Set, the
relay trips onStall Prol. Start”.
Time
Low V Detection
0
1
Reac. Time
Reac. Time timer
starts when low
voltage condition is
detected. During
this period Stall
function is disabled .
Time
1
0
High V Detection
Reac. Long Time
t
2
At the time t
2
when the timer
is timed out and the voltage
has remained below High V
Set, Auto Re-Start is disabled.
P4964ENa
Figure 78: Automatic restart failed- voltage restored after the set time
If v
oltage is not restored within Reac. Long Time duration or if it falls below “High V Set” threshold before Reac.
Shed Time timer has timed out (where Reac. Shed Time timer is set to a value other than zero for sequence start
scheme), Auto Re-Start KO becomes asserted. For default LED and Output Relay management refer to the default
PSL.
14.8 APPLICATION NOTES
14.8.1 START/STALL PROTECTION
When a motor starts it draws a value of current in excess of full load rating for a set period of time, namely the
star
ting time. It is normal practice to assume a constant starting current for the whole of the starting time.
The starting current varies depending on the type and method of starting utilized. If the motor is started direct-on-
line (DOL), the current could easily reach 6 times full load current. However, when star/delta starting is utilized, the
starting current is Ö3 less than when DOL starting.
Chapter 6 - Current Protection Functions P24xM
154 P24xM-TM-EN-2.1

Table of Contents

Related product manuals