Figure 42: Earth fault in Petersen Coil earthed system
Consider a radial distribution system ear
thed using a Petersen Coil with a phase to earth fault on phase C, shown
in the figure below:
V00632
I
A1
I
B1
I
R1
-jX
C1
I
H1
I
A2
I
B2
I
R2
I
L
-jX
C2
jXL
I
H 2
I
A3
IB3
IC3 = IF
-jX
C3
I
R3
I
F
IH3
I
H1
+ I
H2
I
L
= I
F
+ I
H1
+ I
H2
+ I
H3
Figure 43: Distribution of currents during a Phase C fault
Assuming that no r
esistance is present in X
L
or X
C
, the resulting phasor diagrams will be as shown in the figure
below:
Chapter 6 - Current Protection Functions P24xM
116 P24xM-TM-EN-2.1