GE P24DM - IEC 61850 Protocol Blocking; Read-Only Settings; Read-Only DDB Signals

GE P24DM
600 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The following commands are still allowed:
R
ead settings, statuses, measurands
Read records (event, fault, disturbance)
Time Synchronisation
Change active setting group
7.3 IEC 61850 PROTOCOL BLOCKING
If Read-Only Mode is enabled for the Ethernet interfacing with IEC 61850, the following commands are blocked at
the inter
face:
All controls, including:
Enable/disable protection
Operate Control Inputs
CB operations (Close/Trip, Lock)
Reset LEDs
The following commands are still allowed:
Read statuses, measurands
Generate reports
Extract disturbance records
Time synchronisation
Change active setting group
7.4 READ-ONLY SETTINGS
The following settings are available for enabling or disabling Read Only Mode.
RP1 R
ead Only
RP2 Read Only (only for products that have RP2)
NIC Read Only (where Ethernet is available)
7.5 READ-ONLY DDB SIGNALS
The remote read only mode is also available in the PSL using three dedicated DDB signals:
RP1 R
ead Only
RP2 Read Only (only for products that have RP2)
NIC Read Only (where Ethernet is available)
Using the PSL, these signals can be activated by opto-inputs, Control Inputs and function keys if required.
P24xM Chapter 16 - Communications
P24xM-TM-EN-2.1 359

Table of Contents

Related product manuals