EasyManuals Logo

GE P24DM User Manual

GE P24DM
802 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
Figure 197: Autoreclose Shot Counters logic diagram (Module 41) 337
Figure 198: CB Control logic diagram (Module 43) 338
Figure 199: Circuit Breaker Trip Time Monitoring logic diagram (Module 53) 339
Figure 200: AR Lockout Logic Diagram (Module 55) 340
Figure 201: Reset Circuit Breaker Lockout Logic Diagram (Module 57) 341
Figure 202: Pole Discrepancy Logic Diagram (Module 62) 342
Figure 203: Circuit Breaker Trip Conversion Logic Diagram (Module 63) 343
Figure 204: Check Synchronisation Monitor for CB closure (Module 60) 344
Figure 205: Voltage Monitor for CB Closure (Module 59) 345
Figure 206: Three-phase Autoreclose System Check Logic Diagram (Module 45) 347
Figure 207: CB Manual Close System Check Logic Diagram (Module 51) 348
Figure 208: Circuit Breaker Fail logic - part 1 357
Figure 209: Circuit Breaker Fail logic - part 2 358
Figure 210: Circuit Breaker Fail logic - part 3 359
Figure 211: Circuit Breaker Fail logic - part 4 360
Figure 212: CB Fail timing 362
Figure 213: Phase Overcurrent Protection logic diagram 368
Figure 214: Negative Phase Sequence Overcurrent Protection logic diagram 370
Figure 215: IDG Characteristic 373
Figure 216: Earth Fault Protection logic diagram 375
Figure 217: EPATR B characteristic shown for TMS = 1.0 378
Figure 218: Sensitive Earth Fault Protection logic diagram 378
Figure 219: Current distribution in an insulated system with C phase fault 379
Figure 220: Phasor diagrams for insulated system with C phase fault 380
Figure 221: Positioning of core balance current transformers 381
Figure 222: High Impedance REF principle 382
Figure 223: High Impedance REF Connection 383
Figure 224: Thermal overload protection logic diagram 385
Figure 225: Spreadsheet calculation for dual time constant thermal characteristic 386
Figure 226: Dual time constant thermal characteristic 386
Figure 227: Broken conductor logic 389
Figure 228: Transient Earth Fault Logic Overview 393
Figure 229: Fault Type Detector Logic 394
Figure 230: Direction Detector Logic - Standard Mode 394
Figure 231: TEFD output alarm logic 394
Figure 232: Undervoltage - single and three phase tripping mode (single stage) 399
Figure 233: Overvoltage - single and three phase tripping mode (single stage) 402
Figure 234: Residual Overvoltage logic 406
Figure 235: Residual voltage for a solidly earthed system 407
Figure 236: Residual voltage for an impedance earthed system 408
Table of Figures P543i/P545i
xxx P54x1i-TM-EN-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P24DM and is the answer not in the manual?

GE P24DM Specifications

General IconGeneral
BrandGE
ModelP24DM
CategoryControl Unit
LanguageEnglish

Related product manuals