GE P24DM - European Standards; Figure 21: IEC 60255 IDMT Curves

GE P24DM
600 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1000.00
100.00
10.00
1.00
0.10
10
100
Operating time (seconds)
Current (multiples of I
S
)
Standard Inverse (SI)
Very Inverse (VI)
Extremely Inverse (EI)
E00600
1
Long Time LTIInverse ( )
Figure 21: IEC 60255 IDMT curves
3.1.2 EUROPEAN STANDARDS
The IEC 60255 IDMT Operate equation is:
t T
M
L C
op
=
+
+
β
α
1
and the IEC 60255 IDMT Reset equation is:
t T
M
r
=
β
α
1
where:
t
op
is the operating time
t
r
is the reset time
T is the Time Multiplier setting
M is the ratio of the measured current divided by the threshold current (I/Is)
β is a constant, which can be chosen to satisfy the required curve characteristic
α is a constant, which can be chosen to satisfy the required curve characteristic
C is a constant for adding Definite Time (Definite Time adder)
L is a constant (usually only used for ANSI/IEEE curves)
The constant values for the IEC IDMT curves are as follows:
Curve Description
b
constant a constant
L constant
IEC Standard Inverse Operate 0.14 0.02 0
IEC Standard Inverse Reset 8.2 6.45 0
P24xM Chapter 6 - Current Protection Functions
P24xM-TM-EN-2.1 87