EasyManua.ls Logo

GE P24DM - Figure 52: Distribution of Currents During a C Phase to Earth Fault; Figure 53: Theoretical Case - no Resistance Present in XL or XC

GE P24DM
600 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V00632
I
A1
I
B1
I
R1
-jX
C1
I
H1
I
A2
I
B2
I
R2
I
L
-jX
C2
jXL
I
H 2
I
A3
IB3
IC3 = IF
-jX
C3
I
R3
I
F
IH3
I
H1
+ I
H2
I
L
= I
F
+ I
H1
+ I
H2
+ I
H3
Figure 52: Distribution of currents during a C phase to earth fault
The figur
e below shows vector diagrams for the previous system, assuming that it is fully compensated (for
example, coil reactance fully tuned to system capacitance), in addition to assuming a theoretical situation where
no resistance is present either in the earthing coil or in the feeder cables.
V00633
V
res
= -3V
o
I
R1
= I
H1
I
a1
I
b1
V
res
= -3V
o
I
R3
= I
F
+ I
H3
I
L
-I
H1
-I
H2
I
R3
= I
L
- I
H1
- I
H2
a) Capacitive and inductive currents
C B
A 3V0
I
H3
I
H2
IL
I
H1
I
B1
IA1
N
b) Unfaulted line c) Faulted line
Figure 53: Theoretical case - no resistance present in XL or XC
W
ith reference to the associated vector diagram, it can be seen that the the C-phase to earth fault causes the
voltages on the healthy phases to rise by a factor of 3. The A phase charging currents (Ia1, Ia2 and Ia3), are then
shown to be leading the resultant A phase voltage by 90° and likewise for the B phase charging currents with
respect to the resultant Vb.
Chapter 6 - Current Protection Functions P24xM
126 P24xM-TM-EN-2.1

Table of Contents

Related product manuals