E00728
Figures based
on equation
Figure 225: Spreadsheet calculation for dual time constant thermal characteristic
1
10
100
1000
10000
100000
1 10
Current as a Multiple of Thermal Setting
O
p
e
r
a
t
i
n
g
T
i
m
e
(
s
e
c
o
n
d
s
)
Time constant 1 = 5 mins
Time constant 2 = 120 mins
Pre-overload current = 0.9 pu
Thermal setting = 1 Amp
V00629
Figure 226: Dual time constant thermal characteristic
The current setting is calculated as:
Thermal Trip = Permissible continuous loading of the transformer item/CT ratio.
For an oil-filled transformer with rating 400 to 1600 kVA, the approximate time constants are:
t
1
= 5 minutes
t
2
= 120 minutes
An alarm can be raised on reaching a thermal state corresponding to a percentage of the trip threshold. A typical
setting might be "Thermal Alarm" = 70% of thermal capacity.
Chapter 13 - Current Protection Functions P543i/P545i
386 P54x1i-TM-EN-1