EasyManua.ls Logo

GE P24DM - Positive Sequence Overvoltage Protection; Positive Sequence Overvoltage Implementation; Positive Sequence Overvoltage Logic; Figure 105: Positive Sequence Overvoltage Logic

GE P24DM
600 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 POSITIVE SEQUENCE OVERVOLTAGE PROTECTION
7.1 POSITIVE SEQUENCE OVERVOLTAGE IMPLEMENTATION
Positive Sequence Overvoltage Protection is implemented under the P
OS SEQ O/V heading in the VOLT
PROTECTION Voltage column of the relevant settings group.
The product provides two stages of Positive Sequence Overvoltage protection with independent time delay
characteristics.
Stage 1 provides a choice of operate characteristics, where you can select between:
An IDMT characteristic
DT (Definite Time)
You set this using the V1>1 Function cell.
The IDMT characteristic is defined by the following formula:
t = K/( M-1)
where:
K = Time multiplier setting
t = Operating time in seconds
M = Measured voltage / IED setting voltage
There is no Timer Hold facility for Positive Sequence Overvoltage.
Stage 2 can have definite time characteristics only. This is set in the V1>2 status cell.
Two stages are included in order to provide multiple output types, such as alarm and trip stages.
7.2 POSITIVE SEQUENCE OVERVOLTAGE LOGIC
V00817
V1
V1>1 Voltage Set
&
V1>1 Time Delay
V1>1 Trip
V1>1 Start
&
V1>1 Timer Block
V 1>1 Poledead Inh
Enabled
All Poles Dead
&
Note: This diagram does not show all stages . Other stages follow similar principles.
VTS Fast Block only applies for directional models .
VTS Fast Block
&
VTS Blocks 1
Enabled
Figure 105: Positive Sequence Overvoltage logic
P24xM Chapter 10 - Voltage Protection Functions
P24xM-TM-EN-2.1 217

Table of Contents

Related product manuals