16.6 SURGE IMMUNITY TEST
Compliance IEC 61000-4-5: 2005 Level 4, IEC 60255-26:2013
Pulse duration Time to half-value: 1.2/50 µs
Between all groups and protective earth conductor terminal Amplitude 4 kV
Between terminals of each group (excluding communications ports,
where applicable)
Amplitude 2 kV
16.7 IMMUNITY TO RADIATED ELECTROMAGNETIC ENERGY
Compliance IEC 60255-22-3: 2007, Class III, IEC 60255-26:2013
Frequency band 80 MHz to 3.0 GHz
Spot tests at 80, 160, 380, 450, 900, 1850, 2150 MHz
Test field strength 10 V/m
Test using AM 1 kHz @ 80%
Compliance IEEE/ANSI C37.90.2: 2004
Frequency band 80 MHz to 1 GHz
Spot tests at 80, 160, 380, 450 MHz
Waveform 1 kHz @ 80% am and pulse modulated
Field strength 35 V/m
16.8 RADIATED IMMUNITY FROM DIGITAL COMMUNICATIONS
Compliance IEC 61000-4-3: 2006, Level 4, IEC 60255-26:2013
Frequency bands 800 to 960 MHz, 1.4 to 2.0 GHz
Test field strength 30 V/m
Test using AM 1 kHz / 80%
16.9 RADIATED IMMUNITY FROM DIGITAL RADIO TELEPHONES
Compliance IEC 61000-4-3: 2006, IEC 60255-26:2013
Frequency bands 900 MHz and 1.89 GHz
Test field strength 10 V/m
16.10 IMMUNITY TO CONDUCTED DISTURBANCES INDUCED BY RADIO FREQUENCY
FIELDS
Compliance IEC 61000-4-6: 2008, Level 3, IEC 60255-26:2013
Frequency bands 150 kHz to 80 MHz
Chapter 21 - Technical Specifications P24xM