MAN0923_Issue 3_04/15 Touchpoint Pro
Operating Instructions
123
8. Maintenance
5. Select CCB Management and click on Conguration Restore
6. Thesystemwilldisplayamessage“PresentcongurationinCCBwillbereplaced,doyouwant
to continue?”
7. Oncetheactionisconrmed,thecongurationrestorationprocessstartsandaprogressmessageis
displayed. The process may take several minutes depending on the system size
8. Oncethecongurationisrestored,itisrecommendedthatacongurationreportiscreatedtoverify
the settings
8.8 Change the SD Card
Note: The system will provide a notication when the SD card is 80% full. You then have the option of
replacing the card with a new one, or cutting and pasting the card contents into a desktop folder and
reusing the same card.
This procedure does not need a password and can be carried out by any trained operator.
To change the SD Card you will need an unlocked and empty SD card formatted for Windows.
1. From the System Status screen, select Extras, then SD Card
2. Select Eject SD Card
3. When prompted, remove the SD Card and immediately insert a replacement card
Note: Touchpoint Pro has a temporary internal memory so no data is lost during card replacement
4. Return to the Extras screen and select SD Cardagain.ConrmthattheSDCardshowsstatus
“Inserted” and usage below 80%
8.9 Calibrate mV input channels
Catalytic sensors should be calibrated periodically according to the manufacturer’s recommendations.
Note: Engineer level access is required
Note: If you wish to enable a calibration reminder for the channel, please edit this setting before starting
calibration (see Commissioning, Editing a Congured Channel and Congurable Parameter Reference
Guide, Calibration Reminder Settings)
Touchpoint Pro tracks and monitors the ageing of catalytic bead detectors and can provide a warning when
asensorshouldbereplaced.SelectFirstSpanwhencalibratinganeworreplacementsensorfortherst
time, and Span for all calibrations thereafter. When the sensitivity of the sensor has dropped below 50% of
the original value, a “Sensor Lifetime Expired” warning will be generated.
Caution: If First Span is not used, the system will compare the sensitivity of the sensor to the
default value of 50 mV. This may result in the “Sensor Lifetime Expired” warning being generated
prematurely or not at all.
To calibrate a mV input channel, please follow the procedure below in combination with the relevant
instructions in the sensor manual.

Table of Contents

Other manuals for Honeywell touchpoint Pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell touchpoint Pro and is the answer not in the manual?

Honeywell touchpoint Pro Specifications

General IconGeneral
BrandHoneywell
Modeltouchpoint Pro
CategoryControl Systems
LanguageEnglish

Related product manuals