MAN0923_Issue 3_04/15 Touchpoint Pro
Operating Instructions
44
4. Electrical Installation
WARNING
Installation must be in accordance with the recognized standards of the appropriate authority
in the country concerned. Refer to local, national and company regulations.
4.1 Power Consumption
Thepowerconsumptionofyoursystemwascalculatedwhenitwasordered.PleaserefertotheCerticate
of Conformity supplied, or the rating plate for the power consumption.
4.2 Power Supply
WARNING
All power supplies must be hard wired and must include a circuit breaker (RCD / RCCB), and
(close by and unobstructed) a means of manually isolating and locking out the power supply
without breaking the true earth (ground) connection.
Removable plug and socket connection is not permitted under any circumstance.
4.2.1 AC Power Input
AC Power input (if used) must be single phase, 100 -- 240 Vac, 50/60 Hz.
The mains supply requires an overcurrent protection rated in accordance with the rating plate on the
specicsystem.Thesupplymustbeaxedinstallation,i.e.notplugandsocket.Thesupplymustbe
able to be isolated by means of a switch or circuit breaker, which must be suitably located, easily reached
and clearly marked as the Touchpoint Pro disconnect device. The wiring used between the isolator and
Touchpoint Pro must be appropriately rated and approved.

Table of Contents

Other manuals for Honeywell touchpoint Pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell touchpoint Pro and is the answer not in the manual?

Honeywell touchpoint Pro Specifications

General IconGeneral
BrandHoneywell
Modeltouchpoint Pro
CategoryControl Systems
LanguageEnglish

Related product manuals