If Block Active is set to 1, the Controller processes the request. If Block Active is set to 0 the Controller will
not process the request or has already processed the request.
The options for Channel Type are 105 – Input Channel, 111 – Output Channel and 6 – Global (all channels).
IftheCommandDataissetto0,thecommandwillapplytoallthechannelalarmsifaspecicchannelis
identied,ortoallchannelsifthechanneltypeisGlobal.
14.7 Exception Responses
The Modbus exception response is detailed in the Modicon Modbus manual. Any
one of the following exception responses may be returned by the Touchpoint Pro Modbus interface:
Exception Description
01 ILLEGAL FUNCTION Only Modbus functions 02, 03, 04 and 06 are supported. This response is returned if any other
requests are received.
02 ILLEGAL DATA ADDRESS The register addresses supported by each function are listed in this chapter. Any attempt to access a
register outside of these ranges will result in this error.
03 ILLEGAL DATA VALUE This exception is returned if the request has the incorrect length, or if the maximum number of
registers is exceeded. The maximum number of registers that can be requested by function 02 is
512, function 04 is 64, and function 03 is 36 for the Query poll block or 6 for the Command poll
block.
06 SLAVE DEVICE BUSY Applies to function 06 only. Once a poll or command block’s active register has been set, its contents
must not be changed until the main program has carried out the request. This exception is returned if
any attempt is made to change an active poll or command block.
Note: A function 06 that leaves the block unchanged will not generate this error
14. Appendix 1 - Modbus Option

Table of Contents

Other manuals for Honeywell touchpoint Pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell touchpoint Pro and is the answer not in the manual?

Honeywell touchpoint Pro Specifications

General IconGeneral
BrandHoneywell
Modeltouchpoint Pro
CategoryControl Systems
LanguageEnglish

Related product manuals