EasyManua.ls Logo

Honeywell touchpoint Pro - Page 63

Honeywell touchpoint Pro
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAN0923_Issue 3_04/15 Touchpoint Pro
Operating Instructions
63
4. Electrical Installation
Theauxiliaryvoltagesupplycanprovide18-32Vdc(24Vdcnominal)totheelddevicesatamaximum
current of 1.5 A per channel, with the additional limitation that the total current drawn from the module must
not exceed 1.5 A. The supply is short circuit protected – if a short circuit is detected the supply to all four
channels will be disconnected to prevent damage to the module. If the cause of the short circuit is removed,
the auxiliary voltage supply will be restored automatically.
Terminal Identication Label Channel
1 NO Relay 1
2 NC
3 C
4 NO Relay 2
5 NC
6 C
7 NO Relay 3
8 NC
9 C
10 NO Relay 4
11 NC
12 C
13 V Aux 1
14 +V
15 -V
16 V Aux 2
17 +V
18 -V
19 V Aux 3
20 +V
21 -V
22 V Aux 4
23 +V
24 -V
Note: Relay contacts are shown in the shelf state (not powered)

Table of Contents

Other manuals for Honeywell touchpoint Pro

Related product manuals