5.3 PLC Side Setting
5.3.1 Connecting to MELSECNET/H network module
5 - 27
1
OVERVIEW
2
BUS CONNECTION
3
DIRECT CONNECTION
TO CPU
4
COMPUTER LINK
CONNECTION
5
MELSECNET/10
CONNECTION (PLC TO
PLC NETWORK)
6
CC-Link CONNECTION
(INTELLIGENT DEVICE
STATION)
7
CC-Link CONNECTION
(Via G4)
8
ETHERNET
CONNECTION
(2) Network range assignment
: Necessary : As necessary : Not necessary
*1 Be sure to set it to perform the cyclic transmission.
*2 Set it when the MELSECNET/H network module is used in the redundant QnPRHCPU system.
When changing the network parameter
After writing the network parameter to the PLC CPU, operate the PLC CPU ether
turning OFF and then ON or resetting.
Item Setting
Setting necessity at GOT
connection
Monitoring time 200
LB/LW setting
*1
Send range
for station
(LB)
Station
No.1
Start 0000H
End 00FFH
Station
No.2
Start 0100H
End 01FFH
Send range
for station
(LW)
Station
No.1
Start 0000H
End 00FFH
Station
No.2
Start 0100H
End 01FFH
Pairing setting
*2
Disable
LX/LY setting
*1
No setting
Specify I/O master station
*1
No setting
Specify reserved station No setting
Supplementary setting
(Use default value)
Station inherent parameters