5.3 PLC Side Setting
5.3.3 Connecting to MELSECNET/10 network module (A Series)
5 - 39
1
OVERVIEW
2
BUS CONNECTION
3
DIRECT CONNECTION
TO CPU
4
COMPUTER LINK
CONNECTION
5
MELSECNET/10
CONNECTION (PLC TO
PLC NETWORK)
6
CC-Link CONNECTION
(INTELLIGENT DEVICE
STATION)
7
CC-Link CONNECTION
(Via G4)
8
ETHERNET
CONNECTION
(5) Mode setting switch
: Necessary : As necessary : Not necessary
(6) Condition setting switches
: Necessary : As necessary : Not necessary
*1 The MELSECNET/10 network module can be communicated by default parameters.
For details, refer to the following manual.
Type MELSECNET/10 Network system (PLC to PLC network) Reference Manual
When the switch setting (other than the LED indication select switch) is changed
Turn the PLC CPU OFF then ON again, or reset the PLC CPU.
Mode setting switch
Description
Setting
Setting necessity at GOT
connection
Mode setting
(Online)
0 (fixed)
Condition setting switches
Setting
switch
Description
Setting
Setting necessity at GOT
connection
SW1
Network type
(PLC to PLC network (PC))
OFF (fixed)
SW2
Station type
(Control station (MNG))
ON (fixed)
SW3
Parameter for using
*1
(common parameter (PRM))
OFF (fixed)
SW4
No. of stations
*1
OFF (fixed)
SW5
SW6
Total B/W points
*1
OFF (fixed)
SW7
SW8 Not used
OFF (fixed)
F
7
E
6
D
5
C
4
B
3
A
2
9
1
0
8
MODE
0:ONLINE(A.R)
2:OFFLINE
OFF ON
SW
1
2
3
4
5
6
7
8