3 - 2
3.1 SoftGOT-GOT Link Function
3.1 SoftGOT-GOT Link Function
3.1.1 SoftGOT-GOT link function setting
The authorization of the SoftGOT-GOT link function can be set, and the exclusive authorization can be obtained or released.
Only the GOT can obtain the exclusive authorization.
While the GOT has the exclusive authorization, GT SoftGOT2000 cannot obtain the authorization.
For the details of the SoftGOT-GOT link function, refer to the following.
âž GT SoftGOT2000 Version1 Operating Manual
3.1.2 Display operation of the SoftGOT-GOT link function setting
Function Description Setting range
Exclusive
authorization
obtained state
The status whether or not the GOT obtains the exclusive authorization is displayed.
Obtaining or releasing the exclusive authorization can be executed by the GOT.
Obtain/Release
<At GOT startup: Release>
Authorization
obtained time
The time length from the last operation of GT SoftGOT2000 after obtaining the authorization until
the GOT automatically obtains the authorization can be set.
0 to 3600 seconds
<At factory shipment: 60
seconds>
Operating priority
guaranteed time
The time period that the authorized equipment (GOT or GT SoftGOT2000) keeps the
authorization after the last operation of the authorized equipment can be set.
(The unauthorized equipment cannot obtain the authorization until the set time elapses.)
0 to 3600 seconds
<At factory shipment: 0
seconds>
Operation status
popup notification
When the authorization is not obtained in GT SoftGOT2000/GOT, whether to display or not the
information of the authorized side in pop-up can be set.
YES/NO
<At GOT startup: NO>
SoftGOT-GOT link function
Special function setting
Touch
[SoftGOT-GOT link function].