7 - 4
7.3 BootOS and System Application Installation Using Data Storage
7.3 BootOS and System Application Installation Using Data Storage
There are the following two types for the installation of BootOS and system applications using a data storage.
(1) Installing when starting the GOT
7.3.1 Installing when starting the GOT
All the system applications and project data stored in the data storage are transferred to the GOT when powering on
the GOT. This installing method is effective in the following cases.
The GOT utility cannot be displayed.
The system application is not installed.
(2) Installing using the data control function (Utility)
7.3.2 Installing using the data control function (Utility)
By operating the utility, select the system application or project data stored in the data storage and transfer them to
the GOT.
POINTPOINTPOINT
Precautions on installing BootOS, system applications
(1) Installing both BootOS and system applications
After completing BootOS installation, install system applications. When installing BootOS,
the built-in flash memory in the GOT is initialized and goes to the status at factory shipment.
(All system applications and project data are erased.)
(2) Copying project data using a data storage
After installing BootOS and system applications, download the project data.
At this time, match the version of the system application in the GOT with the version of the
system application with which the project data was created.
(3) When system applications and project data are in the data storage (when using GT
Designer3)
For S.MODE switch-pressing installation, after the system application installation has
completed, the project data is downloaded.
When installing with the utility, install the system application and download the project data
from their respective operation screens.
(4) Installation cannot be interrupted.
Do not perform any of the following during a BootOS or system application installation.
Failure to do so may result in installation failure, causing the GOT malfunction.
Powering off the GOT
Pressing the reset button of the GOT
Opening the cover of the SD card interface
Removing the data storage
If the installation failure and the GOT malfunction occur, take the following action.
If BootOS installation failed:
Touch the screen according to the displayed dialog to restart the GOT.
After restarting the GOT, the GOT is initialized to be the factory shipment status.
If the basic system application installation failed:
Install BootOS.
7.3.1 Installing when starting the GOT
BootOS is installed in the GOT at factory shipment. It is not necessary to
install BootOS when not upgrading it.

Table of Contents

Other manuals for Mitsubishi GOT2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi GOT2000 Series and is the answer not in the manual?

Mitsubishi GOT2000 Series Specifications

General IconGeneral
Power Supply24VDC
SoftwareGT Works3
ProcessorRISC CPU
InterfaceEthernet, USB, RS-232, RS-422/485
Operating Temperature0°C to 50°C
Display TypeTFT LCD
Storage Temperature-20°C to 60°C
Humidity10% to 90% (non-condensing)
Shock Resistance147 m/s² (15G), 11ms duration
Touch PanelAnalog Resistive