5 SEQUENCE INSTRUCTIONS
5.3 Output Instructions
121
5
Precautions
When write during RUN is completed for a circuit including a rising edge instruction (LDP/ANDP/ORP instruction), the
instruction is not executed regardless of the ON/OFF status of the target device of the rising edge instruction. Also, in the
case of a rising edge instruction (PLS instruction), the instruction is not executed regardless of the ON/OFF status of the
device that is set as the operation condition. The instruction is executed when the target device and the device in the
operation conditions is set from OFF to ON again.
Note that the device specified by (d) sometimes turns ON for one scan or more when the PLS instruction is made to jump
by the CJ instruction or the executed subroutine program was not called by the CALL(P) instruction.
Operation error
There is no operation error.