7 APPLICATION INSTRUCTION
7.19 Clock instruction
599
7
Comparing clock data zones
TZCP(P)
This instruction compares two comparison time (comparison time zone) specified by (s1) and (s2) with the time data specified
by (s3), and turns on or off the specified bit devices (d) according to the comparison results.
Setting data
Descriptions, ranges, and data types
Applicable devices
Processing details
This instruction compares two comparison time (comparison time zone) specified by (s1) and (s2) with the time data
specified by (s3), and turns on or off the specified bit devices (d) according to the comparison results.
Even if the command contact turns off from on and the TZCP instruction is not executed, (d), (d)+1, and (d)+2 hold the
status before the command contact turned off.
Ladder diagram Structured text
ENO:=TZCP(EN,s1,s2,s3,d);
ENO:=TZCP(EN,s1,s2,s3,d);
Operand Description Range Data type Data type (label)
(s1) Specify the lower limit of time comparison (hour, minute, and
second).
16-bit signed binary ANY16
(s2) Specify the upper limit of time comparison (hour, minute, and
second).
16-bit signed binary ANY16
(s3) Specify the time data (hour, minute, and second). 16-bit signed binary ANY16
(d) Specify the Bit device that turns on/off depending on the
comparison result
Bit Bit
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB
U\G T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U\G Z LC LZ K, H E $
(s1) 
(s2) 
(s3) 
(d) 
(s1) (s2) (s3) (d)
(s1) (s3)
(s1)+1 (s3)+1
(s1)+2 (s3)+2
(d) = ON
(s1) (s3) (s2)
(s1)+1 (s3)+1 (s2)+1
(s1)+2 (s3)+2 (s2)+2
(d) +1 = ON
(d) +2 = ON
(s3) (s2)
(s3)+1 (s2)+1
(s3)+2 (s2)+2

Data range
Hour
Minute
Second
Data range
Hour
Minute
Second
Data range
Hour
Minute
Second
Data range
Hour
Minute
Second
Data range
Hour
Minute
Second
Data range
Hour
Minute
Second
Data range
Hour
Minute
Second
(0 to 23)
(0 to 59)
(0 to 59)
(0 to 23)
(0 to 59)
(0 to 59)
(0 to 23)
(0 to 59)
(0 to 59)
(0 to 23)
(0 to 59)
(0 to 59)
(0 to 23)
(0 to 59)
(0 to 59)
(0 to 23)
(0 to 59)
(0 to 59)
(0 to 23)
(0 to 59)
(0 to 59)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC iQ-F FX5 series and is the answer not in the manual?

Mitsubishi MELSEC iQ-F FX5 series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC iQ-F FX5 series
CategoryController
LanguageEnglish

Related product manuals