EasyManuals Logo

Mitsubishi MELSEC iQ-F FX5 series User Manual

Mitsubishi MELSEC iQ-F FX5 series
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #365 background imageLoading...
Page #365 background image
7 APPLICATION INSTRUCTION
7.6 Character string operation instruction
363
7
Precautions
• In character string comparison operation, if the target device range does not have "00H", the values until the last number of
the device are retrieved. Thus, even if the target device range does not have "00H", a comparison operation result is output
when a mismatch between the acquired character strings is detected.
• For the data specified by (s1) and (s2) as shown above, the second character is different between them. Thus, the
operation result is non-conductive.
Operation error
There is no operation error.
LD$= D7998
(s1) (s2)
D10
M0
D7998
D7999
42H(B) 41H(A)
44H(D) 43H(C)
D10
D11
5A(Z) 41H(A)
00H 43H(C)
[Example]
Data of (s1) Data of (s2)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC iQ-F FX5 series and is the answer not in the manual?

Mitsubishi MELSEC iQ-F FX5 series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC iQ-F FX5 series
CategoryController
LanguageEnglish

Related product manuals