502
7 APPLICATION INSTRUCTION
7.12 Shortcut control instruction
Operation error
Error code
(SD0/SD8067)
Description
1811 The number of the ROTC instructions which are used simultaneously exceeds four.
2820 The device range specified by (s) exceeds the corresponding device range.
The device range specified by (d) exceeds the corresponding device range.
3405 The value specified by (n1) is outside the following range.
2 to 32767
The value specified by (n2) is outside the following range.
0 to 32767
The value specified by (n1) or (n2) is in the following condition.
(n1) < (n2)
Either (s), (s)+1, or (s)+2 is negative.
Either (s), (s)+1, or (s)+2 is equal to (n1) or larger.