7 APPLICATION INSTRUCTION
7.14 Pulse related instruction
537
7
Operation error
Error code
(SD0/SD8067)
Description
1810 The output destination specified by (d) is already used by another instruction (positioning instruction).
(The PMW output is not executed.)
A Y device is specified as the output destination specified by (d), and there is no unused channel number in the parameter setting
3405 Y10 or later is specified as the output destination specified by (d).
(The PMW output stops.)
3600 A channel number that is not selected in the parameter setting are specified for the output destination specified by (d).
(The PMW output is not executed.)
3611(CH1)
3612(CH2)
3613(CH3)
3614(CH4)
The ON time specified by (s1) is larger than the period specified by (s2).
(The PMW output stops.)
In (s1) and (s2), a negative value is specified.
(The PMW output stops.)
Values of an SD device for setting pulse width and period of this instruction are incorrect.
(The PMW output stops.)
The ON time or period is less than “1”.
The SD device specified for the number of output pulses stores a value outside the available range (0 to 2,147,483,647).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC iQ-F FX5 series and is the answer not in the manual?

Mitsubishi MELSEC iQ-F FX5 series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC iQ-F FX5 series
CategoryController
LanguageEnglish

Related product manuals