EasyManua.ls Logo

Siemens SINAMICS G120 - Page 381

Siemens SINAMICS G120
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
381
Table 12- 7 PM230, IP20, Frame Sizes C, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
6SL3210…
6SL3210…
…1NE22-6UL0
…1NE22-6AL0
…1NE23-2UL0
…1NE23-2AL0
…1NE23-8UL0
…1NE23-8AL0
LO power
LO input current
LO output current
11 kW
26.9 A
26 A
15 kW
33.1 A
32 A
18.5 kW
39.2 A
38 A
HO power
HO input current
HO output current
7.5 kW
18.6 A
18 A
11 kW
26.9 A
26 A
15 kW
33.1 A
32 A
Fuse according to IEC
Fuse according to UL
3NE1 803-0
AJT35 / 3NE1 803-0
3NE1 817-0
AJT45 / 3NE1 817-0
3NE1 817-0
AJT50 / 3NE1 817-0
Power loss
0.3 kW
0.35 kW
0.45 kW
Required cooling air flow
18.5 l/s
18.5 l/s
18.5 l/s
Cross section of line and motor cables 6 …16 mm
2
106 AWG
6 …16 mm
2
106 AWG
6 …16 mm
2
106 AWG
Tightening torque for line and motor cables
1.3 Nm / 12 lbf in
1.3 Nm / 12 lbf in
1.3 Nm / 12 lbf in
Weight, unfiltered
Weight, filtered
4.5 kg
5.1 kg
4.5 kg
5.1 kg
4.5 kg
5.1 kg
Table 12- 8 PM230, PT, Frame Sizes C, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
6SL3211…
6SL3211…
…1NE23-8UL0
…1NE23-8AL0
LO power
LO input current
LO output current
18.5 kW
39.2 A
38 A
HO power
HO input current
HO output current
15 kW
33.1 A
32 A
Fuse according to IEC
Fuse according to UL
3NE1 817-0
AJT50 / 3NE1 817-0
Power loss
0.45 kW
Required cooling air flow
18.5 l/s
Cross section of line and motor cables 6 …16 mm
2
106 AWG
Tightening torque for line and motor cables
1.3 Nm / 12 lbf in
Weight, unfiltered
Weight, filtered
5.4 kg
6 kg