Technical data
12.2 Technical data, Power Modules
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
381
Table 12- 7 PM230, IP20, Frame Sizes C, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
LO power
LO input current
11 kW
26.9 A
15 kW
33.1 A
18.5 kW
39.2 A
HO power
HO input current
7.5 kW
18.6 A
11 kW
26.9 A
15 kW
33.1 A
Fuse according to IEC
3NE1 803-0
3NE1 817-0
3NE1 817-0
Required cooling air flow
Cross section of line and motor cables 6 …16 mm
2
6 …16 mm
2
6 …16 mm
2
Tightening torque for line and motor cables
Weight, unfiltered
4.5 kg
4.5 kg
4.5 kg
Table 12- 8 PM230, PT, Frame Sizes C, 3 AC 380 V … 480 V
Order No. - without filter
Order No. - with filter
LO power
LO input current
18.5 kW
39.2 A
HO power
HO input current
15 kW
33.1 A
Fuse according to IEC
3NE1 817-0
Required cooling air flow
Cross section of line and motor cables 6 …16 mm
2
Tightening torque for line and motor cables
Weight, unfiltered
5.4 kg