Technical data   
12.2 Technical data, Power Modules 
  Inverter with CU230P-2 Control Units  
382  Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG 
Table 12- 9  PM230, IP20, Frame Sizes D, 3 AC 380 V … 480 V 
Order No. - without filter 
Order No. - with filter 
…
LO power  
LO input current  
22 kW 
42 A 
30 kW 
56 A 
 
HO power  
HO input current  
18.5 kW 
36 A 
22 kW 
42 A 
 
Fuse according to IEC 
3NE1818-0 
3NE1820-0 
 
Required cooling air flow 
Cross section of line and motor cables  16 … 35 mm
2
 
16 … 35 mm
2
 
 
Tightening torque for line and motor cables 
Weight, unfiltered 
11 kg 
11 kg 
 
Table 12- 10  PM230, IP20, Frame Sizes E, 3 AC 380 V … 480 V 
Order No. - without filter 
Order No. - with filter 
…
LO power  
LO input current  
37 kW 
70 A 
45 kW 
84 A 
 
HO power  
HO input current  
30 kW 
56 A 
37 kW 
70 A 
 
Fuse according to IEC 
3NE1021-0 
3NE1022-0 
 
Required cooling air flow 
Cross section of line and motor cables  25 … 50 mm
2 
25 … 50 mm
2 
 
Tightening torque for line and motor cables 
Weight, unfiltered 
15 kg 
15 kg