7-14
You must enable the Expansion Power Supply via the 4010 System Options
menu when installing the expansion power supply. The default setting for the
expansion power supply is OFF.
Use the following steps to set the Expansion Power Supply option on the 4010
FACP.
1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3. Press <ENTER> to continue.
4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<EXPANSION POWER> is displayed and then press <ENTER>.
6. Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then
press Enter.
7. Follow the prompts to confirm this action.
Expansion Power
Overview
Setting the Expansion Power
Option