EasyManua.ls Logo

Simplex 4010 - Silence;Reset Inhibit; Overview; Setting the Silence;Reset Inhibit

Simplex 4010
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-5
You can inhibit the Alarm Silence/System Reset on a 4010 FACP for a set
duration. The range for the Silence/Reset Inhibit timer is 0-60 minutes with zero
(No Inhibit) being the default setting.
Use the following steps to set the Silence/Reset Inhibit timer on the 4010 FACP.
1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3. Press <ENTER> to continue.
4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<SILENCE/RESET INHIBIT> is displayed and then press <ENTER>.
6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 minutes and
then press Enter.
7. Follow the prompts to confirm this action.
Silence/Reset Inhibit
Overview
Setting the Silence/Reset
Inhibit
Pro
g
rammin
g
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Related product manuals