7-5
 
 
You can inhibit the Alarm Silence/System Reset on a 4010 FACP for a set 
duration.  The range for the Silence/Reset Inhibit timer is 0-60 minutes with zero 
(No Inhibit) being the default setting. 
 
Use the following steps to set the Silence/Reset Inhibit timer on the 4010 FACP. 
 
1. Press <MENU>. 
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed 
and then press <ENTER>.  A warning appears, indicating that the 4010 is 
no longer in the Fire Alarm Operation mode. 
3. Press <ENTER> to continue. 
4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is 
displayed and then press <ENTER>. 
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until 
<SILENCE/RESET INHIBIT> is displayed and then press <ENTER>. 
6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 minutes and 
then press Enter. 
7.  Follow the prompts to confirm this action. 
 
 
 
Silence/Reset Inhibit 
Overview 
Setting the Silence/Reset 
Inhibit 
Pro
rammin
 
Technical Manuals Online! - http://www.tech-man.com