EasyManua.ls Logo

Simplex 4010 - Single-Station; Overview; Enabling Single-Station

Simplex 4010
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-15
Single station has the following effect.
Sounder activates when the associated sensor is above its alarm threshold.
Sounder silences when sensor is below its alarm threshold.
Alarm remains at panel until reset is performed.
Use the following steps to set the Single-Station option on the 4010 FACP. The
default setting for this option is ON.
1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3. Press <ENTER> to continue.
4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<SINGLE STATION OVERRIDE> is displayed and then press
<ENTER>.
6. Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then
press Enter.
7. Follow the prompts to confirm this action.
Single-Station
Overview
Enabling Single-Station
Pro
g
rammin
g
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Related product manuals