7-15
Single station has the following effect.
• Sounder activates when the associated sensor is above its alarm threshold.
• Sounder silences when sensor is below its alarm threshold.
• Alarm remains at panel until reset is performed.
Use the following steps to set the Single-Station option on the 4010 FACP. The
default setting for this option is ON.
1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3. Press <ENTER> to continue.
4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<SINGLE STATION OVERRIDE> is displayed and then press
<ENTER>.
6. Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then
press Enter.
7. Follow the prompts to confirm this action.
Single-Station
Overview
Enabling Single-Station
Pro
rammin