B-3
Table B-1. Master Controller Points
Point Type Label Description
0-1 R Front Panel Piezo Indicates the status of the Piezo Sounder on the 4010
Master.
0-2 R External N2 Disconnect
Relay
Indicates the status of the External N2 Disconnect
Relay. Turns on when no slaves are communicating;
turns off on System Reset.
0-3 R Fire LED Status of the front panel Alarm LED.
0-4 R Supervisory LED Status of the front panel Supervisory LED.
0-5 R Trouble LED Status of the front panel Trouble LED.
0-6 R Alarm Silence LED Status of the front panel Alarm Silence LED.
0-7 R AC Power LED Status of the front panel AC Power LED.
0-8 U User LED 1 This point indicates the status and configuration of the
first user programmable LED on the front panel.
0-9 U User LED 2 This point indicates the status and configuration of the
second user programmable LED on the front panel.
0-10 U User LED 3 This point indicates the status and configuration of the
third user programmable LED on the front panel.
0-11 U User Defined Key 1 This point indicates the status and configuration of the
first user programmable key (in the function menu).
0-12 U User Defined Key 2 This point indicates the status and configuration of the
second user programmable key (in the function menu).
0-13 R LCD Backlight Indicates the status of the LCD backlight on the front
panel.
The NAC (Notification Appliance Circuit) Card is required for all 4010
configurations, and is located at Card Address 1. There are seven hardware
points and eight card status points associated with the NAC card.
The NAC Card has eight card status points associated with it. Table B-2
describes the card status points for the NAC card.
Continued on next page
Hardware Points, Continued
Master Controller Points
(continued)
NAC Card
NAC Card Status Points
Hardware/Pseudo Points