B-17
Table B-20 System Pseudo Points (Continued)
Point Type Label Description
D48 W T LCD Annunciator Sounder Disable When on the panel tells all LCD
Annunciators to disable their local
sounder. Turning pseudo off will enable
the sounders. Controllable from front
panel only- not SMPL.
D49 W U IDNet Boost When on it boosts the IDNet levels.
D50 W U Device Almost Dirty When active it forces IDNet almost dirty
troubles to report.
D51 W U TrueAlarm Peak Log Enable When on any peak value change
recorded on IDNet devices is sent to the
Trouble Log.
D52 R U RS232 Port A Disconnected On whenever nothing is connected to Port
A on the RS232 or RS232/Modem card.
D53 R U RS232 Port B Disconnected On whenever nothing is connected to Port
B on the RS232 or RS232/Modem card.
D54-D57 - Reserved System Pseudo Point Unused.
D58 R U Network System Reset
D59 R U Network Signal Silence
D60 - Digital: P60 Unused.
D75 - Digital: P75 Unused.
The user digital pseudo card in the 4010 is at address 19. It has 75 points
available for specialized applications programming. Any point may be
programmed as one of the four types of digital pseudos (i.e. UTILITY, FIRE,
etc.), and each may be assigned a 40 character custom label.
Note that any user pseudo points defined as FIRE type are not auto-generated in
the General Alarm List (L1), and SUPERVISORY points are not generated into
the Supervisory Monitor List (L8).
Continued on next page
Pseudo Points, Continued
4010 System Digital Pseudos
(continued)
4010 User Digital Pseudos
Hardware/Pseudo Points
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing

Related product manuals