7-7
The Door Holder - Alarm Door Drop Timer allows the 4010 to hold doors open
for a set duration during an alarm condition. After that duration has expired, the
4010 shuts off the door holder relays and the doors close. The range for the
timer is 0-60 seconds with a default setting of zero seconds. To have door
holders drop the doors immediately, leave the timer set to zero seconds.
Use the following steps to set the Door Holder Alarm Door Drop timer on the
4010 FACP.
1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3. Press <ENTER> to continue.
4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<DOOR DROP ON ALARM > is displayed and then press <ENTER>.
6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 seconds and
then press Enter.
7. Follow the prompts to confirm this action.