1-5
The following is a list of optional modules for the 4010. Refer to the individual
instructions that accompany each module for more information. Those
instructions and their part numbers are listed in the Related Documentation
section of this chapter. Refer to the label inside the door of the 4010 for the
placement of optional modules.
Note: Certain modules are mutually exclusive. For example:
One DACT or One City Circuit Card is allowed.
One 4120 Network Card or One DACT is allowed.
One Dual RS232 Card or One RS232/Modem is allowed.
One Battery Meter Module or One 24VDC Extender Terminal
Block.
The 4010 has five dedicated mounting locations to support the following
modules.
4010-9806 Class A Adapter Card for NACs
The four NACs found on the SFI/O board are Class B (Style Y). To support
Class A (Style Z) you must install an adapter card that mounts to the SFI/O
board. Each adapter card supports two NACs.
4010-9809 City Circuit Card
The city circuit card connects to the SFI/O with a ribbon harness to provide UL-
listed connections to either Remote Station (reverse polarity) or Public Service Fire
Communications Center (local energy) receiving units (selectable). The card has
two circuits -- Circuit 1 reports only alarm events and Circuit 2 can be configured
to report Trouble events or Trouble and Supervisory events. In the event of a CPU
failure, a city card configured for a Trouble Output sends a trouble to the city
circuit. The card is mounted to the right of the SFI/O at the top of the chassis.
Newer versions of the 4010 FACP (Version 2.01 or later) provide the ability to
reset the City Circuit in the following situation.
If the device(s) in alarm is physically removed.
No other devices are in an alarm state.
System Reset is performed.
Enabling City Circuit reset is done via Custom Control. Refer to Application-
Specific Examples at the end of Chapter 8 for specific information. Be sure to
consult the AHJ before enabling the City Circuit Reset option.
Continued on next page
Optional System Modules
Overview
Optional Modules with
Dedicated Hardware Slots
Overview
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
BrandSimplex
Model4010
CategoryFire Alarms
LanguageEnglish

Related product manuals