Walk Test allows one person to test the functionality of the 4010. Once the
panel is placed into Walk Test mode, any device can be tested in any order. For
each device, you should simulate both an alarm and trouble. If an audible or
visible indication is used, wait for the indication before moving on to the next
device. Walk Test options are viewed by selecting the WalkTest entry at the
main menu. The Walk Test screens allow you to customize the Walk Test
operation. The signals (if enabled) annunciate device coding for Walk Test. Earth
Faults are signaled during Walk Test on both the front panel display/tone-alert and
by activating audible and visible notification circuits for 4 seconds. Suppression
release outputs are NOT activated by Walk Test.
Walk Test automatically aborts after eight hours and restores the panel to normal
operation.
To activate Walk Test, follow Steps 1 through 5.
1. From the High-Level Status screen, press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [WalkTest] is displayed and then
press <ENTER>.
3. Press <ì> or <ö> to move the focus brackets to the desired option.
4. Press <NEXT> or <PREVIOUS> to scroll through the following choices:
• On/Off  Walk Test mode.
• Log/No Log  allows events to be recorded to the Historical Logs.
• Signal/Silent  activate/deactivate Signals.
5. Press <ENTER> to activate Walk Test.
Continued on next page
Walk Test
Overview
Using Walk Test