7-17
1. Press <MENU>, followed by <NEXT> until Programming is displayed.
Press <ENTER> in response to the prompts to access the Programming
menu.
2. Use the <NEXT> button to move through the Programming menu options.
Press <ENTER> when System Options is displayed.
3. Use the <NEXT> button to move through the System Options menu. Press
<ENTER> when <SUPPRESSION RELEASE> is displayed.
4. At the On/Off Status screen press Enter. Press Next to select ON and then
press Enter. Follow the prompts to activate this function.
5. Press Exit/Clear until the System Options choice is shown.
1. Press Next until the Configure Points choice is shown and then press Enter.
2. Press Next until the TrueAlarm choice is shown and then press Enter.
3. Press Next until Edit TrueAlarm Point is displayed and then press Enter.
4. Press Enter to select the first device shown [3-1]. Press Next until Edit
Point Type is displayed and press Enter.
5. Press Next to scroll through the point types to find the appropriate point
type for your device. The following are monitor point types for suppression
release functions.
• SUPDET Suppression Release detector zone
• SUPABRT Suppression Release abort zone
• SUPDUMP Suppression Release manual dump
• SUPPRES Suppression Release pressure monitor
Once the appropriate point type is displayed, press Enter to assign that point
type to the device at address [3-1]. Follow the prompts to confirm this
selection.
6. Press Exit/Clear until Configure Point: TrueAlarm is displayed.
This section describes adding Suppression Release monitor points to a
Suppression Release list.
1. Press Next until Lists is displayed and then press Enter.
2. Press Next until the desired list is displayed. The following are the choices
for your suppression release lists. L9 through L11 are your suppression
initiating device lists.
- L9 Automatic Suppression Release Points
- L10 Suppression Manual Release Points
- L11 Suppression Release Abort Points
- L12 Suppression Release Output Points
Once the appropriate list is displayed, press Function.
Continued on next page
Suppression Release, Continued
Step 1. Turn ON Suppression
Release
Step 2. Assign Suppression
Monitor Point Types to
Suppression Release Monitor
Points
Step 3. Create Suppression
Release Monitor Lists
Pro
g
rammin
g
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
BrandSimplex
Model4010
CategoryFire Alarms
LanguageEnglish

Related product manuals