8-3
The following is a list of valid Input Opcodes, Input Operators, and Relational
Operators for the 4010 Custom Control option.
Table 8-1. Input Opcodes
Input Opcodes Description
FIRE DETECT Fire Detect State
FIRE Fire State
FIRE ACK Fire Acknowledge State (needs ACK)
SUPV Supervisory State
SUPV ACK Supervisory Acknowledge State
TBL Trouble State
TBL ACK Trouble Acknowledge State
PHY NORM Physically Normal State
PHY ABN Physically Abnormal State
PHY OPEN Physically Open State
PHY SHORT Physically Short State
ABN DET Abnormal Detect State
OPEN DET Open Detect State
SHORT DET Short Detect State
CTRL ON Control ON State
CTRL OFF Control OFF State
DISABLE Disable State
CLASS A TROUBLE Class A Trouble State
ON/CODE On coding State
OFF OFF State
COMP CNST Compare to a Constant Value
COMP VAR Compare to a Variable Value
EMPTY Empty state of a list
ANY Any number of elements in a list
ALL All elements in a list
SAVE Save the state of an equation
RECALL Recall the state of an equation
DELAY CNST Delay for a constant value
DELAY VAR Delay for a variable value
CYCLE CNST Cycle for a constant value
CYCLE VAR Cycle for a variable value
DIRTY Dirty detector state
SMOKE LEV A percentage smoke level
Continued on next page
SMPL Opcodes and Operators
Input Opcodes