1-12
Certain operator functions of the 4010 are passcode protected at different levels.
This section describes logging in and out at specific access levels.
All operations in the 4010 are protected at a preset level with designated
passcodes to access these operations. The table below shows the basic
operations and menu choices for specific access levels. The default passcodes
are listed for Levels 2 through 4. Refer to the Menu Structure later in this
chapter for a complete quick-reference of the main 4010 FACP menus.
Table 1-2. Access Levels and Operations
ACCESS LEVEL OPERATIONS
1
Ack
Silence
System Reset
2
Passcode = 2000
All Level 1 Operations, plus:
Set Time/Date
Point Control
Enable/Disable Points
3
Passcode = 3000
All Level 1 & 2 Operations,
plus:
Clear Logs
Clear Verification Tallies
Programming
- Edit/Clear Point Label
- Restore/Save CFIG
TrueTest
Walk Test
Reports
4
Passcode = 4000
All Level 1,2, & 3 Operations,
plus:
Quick CFIG
Run Diagnostics
Upload/Download
Programming
• Edit Cards
• Edit SMPL Program
• System Options
Restart Panel
• Warm Start
• Cold Start
Continued on next page
Passcodes, Access Levels, and Logging In and Out
Overview
Passcodes and Access Levels
Technical Manuals Online! - http://www.tech-man.com