11-5
This section describes how to view and clear the Historical Logs on the 4010.
The 4010 has three logs; Alarm, Supervisory, and Trouble. The logs can be
viewed separately, or they can be viewed in chronological sequence as a single
Combined log. Each log records information about the event and the time the
event occurred. Table 11-1 describes the different logs and their stored events.
Table 11-1. Historical Logs and Events
Historical Log Stored Events
ALOG
Alarm Log (up to 100
entries)
Alarms
Alarm Ack (global only)
Log cleared
Alarm Silence
System Reset
SLOG
Supervisory Log (up to 50
entries)
Supervisory conditions
Supervisory Ack (global only)
Log cleared
TLOG
Trouble Log (up to 300
entries)
All card and system troubles
Login/Logout for Level 2 or higher
Log cleared
Walk Test events (abnormal and
trouble)
TrueAlarm peak values (if selected)
CLOG
Combined Log (all entries)
All Events in chronological order
Figure 11-2 shows an example of an Alarm Log.
Figure 11-2. Sample Alarm Log Screen
Continued on next page
Viewing and Clearing Historical Logs
Overview
ALOG: 1/34 10:09:01 am Wed 14-May-97
Fire Alarm
One of 34 Alarm Log
Entries
Time and Date of Event
Operation
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing