7-11
 
 
This option selects the mode of operation for the 4010 FACP if an alarm occurs 
during an AC power loss while a Depleted Battery trouble exists.  The specific 
operation of this option differs slightly, depending on whether you have a 
domestic or Canadian system. 
 
Domestic Operation.  The default setting for the option is OFF and the 
threshold voltage is 19.4 VDC ± 5%.  Operation of this option for a domestic 
system is as follows: 
 
•  If the system is in alarm and a depleted battery condition occurs, any NACs 
that are active remain active. 
 
•  If the system in not in alarm and a depleted battery condition occurs, the 
NACs are prevented from activating. 
 
Canadian Operation. The default setting for the option is OFF and the 
threshold voltage is 19.4 VDC ± 5%.  Operation of this option for a Canadian 
system is as follows: 
 
•  When a depleted battery condition occurs, power is turned off to the 4010.  
AC power must be restored to re-activate the 4010. 
 
Use the following steps to set the Depleted Battery Cut-Out on the 4010 FACP. 
 
1. Press <MENU>. 
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed 
and then press <ENTER>.  A warning appears, indicating that the 4010 is 
no longer in the Fire Alarm Operation mode. 
3. Press <ENTER> to continue. 
4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is 
displayed and then press <ENTER>. 
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until 
<DEPLETED BATT. CUTOUT> is displayed and then press <ENTER>. 
6. Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then 
press Enter. 
7.  Follow the prompts to confirm this action. 
 
 
 
Depleted Battery Cut-Out 
Overview 
Setting the Depleted Battery 
Cut-Out 
Pro
rammin
 