Page #155 background image
11-7
The 4010 allows you to view each configured point in the system and, depending
on your access level, control and disable/enable the point you are viewing. This
section describes how to view, control, and enable/disable points.
Use the Steps 1 through 5 and Figure 11-4 to Control/View Points in a 4010. A
TrueAlarm device type and point are used as an example in this section.
1. From the High-Level Status screen, press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [Control/View Points] is displayed
and then press <ENTER>.
3. Press <NEXT> or <PREVIOUS> to scroll through the point types until the
desired device type is displayed [TrueAlarm] and then press <ENTER>.
4. Press <NEXT> or <PREVIOUS> to scroll through the points until the
point you wish to view/control is displayed and then press <ENTER>.
5. Press <ENTER> to activate control of that point and to view additional
information about that point. Press <NEXT> or <PREVIOUS> to scroll
through the allowable functions for the point you are viewing.
Figure 11-4. Control/View Points Menu
Continued on next page
Viewing and Controlling Points
Overview
Controlling/Viewing Points
Panel
Restart
• View Additional Info
• Control Points
• Enable/Disable
Top Level Menus
Control/
View Points
Login/
Logout
TrueAlarm
Operation
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
BrandSimplex
Model4010
CategoryFire Alarms
LanguageEnglish

Related product manuals