11-8
The control functions for each point type is listed in Table 11-2.
Table 11-2. Device Type and Control Functions
Device Type Control Functions View Functions
TrueAlarm Control:
• Clear Verification Tally
• Force on Device LED
• Change Sensitivity
• Clear Peak Value
• Change TrueTest State
• Manually Control Sounder, Relay or
Isolator
View:
• Address
• Device Type
• Point Type
• Sensitivity
ZAMS/IAMs Control:
• Clear Verification Tally
• Force on Device LED
• Change TrueTest State
View:
• Address
• Device Type
• Point Type
Relay/RIAMs Control:
• ON/OFF/Auto/Change Priority
Same as ZAMS/IAMS
NACs Control:
• ON/OFF/Auto/Change Priority
Same as ZAMS/IAMS
Digital Pseudos Control:
• ON/OFF/Change Priority
Same as ZAMS/IAMS
Analog Pseudos SET analog value for the point (Range - 0 to
65535)
Same as ZAMS/IAMS
Lists
Control: ON/OFF/Auto
View:
• List Counts
• List Contents
Same as ZAMS/IAMS
24-I/O Inputs Turn on Card LED Same as ZAMS/IAMS
24-I/O Outputs Control:
• ON/OFF/Auto/Change Priority
Same as ZAMS/IAMS
System Points VIEW ONLY, NO CONTROL ALLOWED Same as ZAMS/IAMS
Continued on next page
Viewing and Controlling Points, Continued
Controlling/Viewing Points
(continued)
Technical Manuals Online! - http://www.tech-man.com