Page #185 background imageLoading...
Page #185 background image
B-15
The system digital pseudo card in the 4010 system is located at Card Address 18.
It contains a total of 75 reserved system pseudo points that cannot be edited.
The following table list the system pseudo points. The type field denotes which
class (see above) the point falls into, and what its type is (U =UTIL, F=FIRE,
T=TROUBLE, S=SUPERVISORY).
Table B-20. System Pseudo Points
Point Type Label Description
D1 R U Unacked Fire in System On if unacked fire exists in system.
D2 R U Unacked Supervisory in System On if unacked supervisory exists in
system.
D3 R U Unacked Trouble in System On if unacked trouble exists in system.
D4 R T Extra N2 Card Turned on at panel startup if an
unprogrammed N2 slave card is detected.
Only clears on panel restart.
D5 R T External N2 Trouble Turns on when panel is no longer
communicating with ALL slave cards.
Turns off on a System Reset.
D6 RW U User SMPL Program On when User SMPL program is active.
D7 R T Cold Start Indicates that panel has performed a cold
start. Turns of when acknowledged.
D8 R T Warm Start / Check Time and
Date
Indicates that panel has performed a
warm start. Turns off when
acknowledged.
D9 RW F Manual Evacuation Turns on when Manual Evacuation is
selected. Turns off on a System Reset.
D10 R T System Time and Date Indicates that the time and date is
incorrect. Turns off when time and date is
updated.
D11 R T Simplex Service Mode Indicates that the panel is in Service
Mode. Turns off only on a panel restart.
D12 RW U Keypad Inactivity Timer Disable Disables Keypad Inactivity timer.
D13 R T Active List Overflow Turns on when the number of alarms,
supervisories, or troubles is greater than
the system active list size (100 fires, 50
supv, 300 troubles). Turns off on a panel
restart.
Continued on next page
Pseudo Points, Continued
4010 System Digital Pseudos
Hardware/Pseudo Points
Technical Manuals Online! - http://www.tech-man.com

Table of Contents