4-6
Once this action is selected from the Quick CFIG menu, you can set these
options by scrolling through the choices shown in Table 4-1 and selecting the
appropriate settings for each. For timer options, selecting 0initiates the action
immediately.
1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no
longer in the Fire Alarm Operation mode.
3. Press <ENTER> to continue with the Quick-CFIG option.
4. Press <NEXT> or <PREVIOUS> until <EDIT SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5. Use the <NEXT> and <PREVIOUS> keys to scroll through the system
options. Edit each of the system options as necessary, using the information
in Table 4-1. Refer to Chapter 7 for specific information on system options.
Table 4-1. System Options and Available Settings
System Option Settings
Time/Date Format Choose 12 or 24-Hour Format
Active Status Reminder Choose:
On/Off; default Off
Set Reminder Interval (1-12 Hours); default = 8
Signal Duration (0-60 Secs.) 0=ON til clear
default = 5
Alarm Silence/Reset Inhibit Choose a timer range from 0 - 60 Mins; default = 0
Alarm Cut-out Timer Choose a timer range from 0 - 60 Mins; default = 0
Door Drop on Alarm Choose a timer range from 0 - 60 Secs; default = 0
Door Drop on AC Power Loss Choose a timer range from 0 - 60 Mins; default = 0
Audible NAC Operation Choose:
Audible NACs: Steady
Audible NACs: Slow March
Audible NACs: Fast March
Audible NACs: Temporal (default)
Continued on next page
Edit Settings for System Options
Overview
Procedure
Please Wait . . .
Fire Alarm Operation Suspended
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing

Related product manuals