8-11
AND
The AND Link operator links the current statement in Series with all previous
statements in an equation (see Figure 8-6).
[ ] [ ] [FIRE] [3-01]
[AND] [ ] [FIRE] [3-02]
Figure 8-6
In Figure 8-6, IF the condition of 3-01 is Fire AND the condition of 3-02 is Fire,
then the INPUT SIDE is true. Another way to look at this equation is shown in
Figure 8-7. In order to cross from the INPUT SIDE of the equation to the
OUTPUT SIDE, both of the statements must be true.
18-01 18-02
Figure 8-7
Continued on next page
Custom Control Programming, Continued
Field 1 (continued)
INPUT SIDE
(Statements 1 & 2)
Points 3-01 and 3-
02 in Series.
Both statements
must be true in
order to go from
the INPUT to the
OUTPUT.
OUTPUT SIDE
3-01
Field 1
3-02
Field 2 Field 3
Field 4
FIRST
STATEMENT
SECOND
STATEMENT
Pro
g
rammin
g
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing

Related product manuals