Analog pseudo points exist as counters or timers in the 4010 system. SMPL 
delay and cycle equations may be written referencing the user Analog pseudo 
points on the output side (for delay/cycle operations).  Each analog point may 
contain a value from 0-65,535 and the point is considered ON when the value is 
non-zero.  For delay and cycle purposes, the maximum allowable value gives a 
real-time range of just over 18 hours.  There are two analog pseudo cards in the 
4010 system - one reserved for system analogs, and one reserved for user points. 
 
The 4010 system has one analog pseudo card reserved for system use at Card 
Address 20.  It contains a total of 25 points. At present, only the first seven are 
used but the remainder are reserved for future expansion. 
 
Table B-21. 4010 System Analog Pseudos
 
Point Label  Description 
A1  Fire Count  Number of fire alarms active in system. 
A2  Supervisory Count  Number of supervisory alarms active in system. 
A3  Trouble Count  Number of troubles active in system. 
A4  System Startup  Pulsed for one poll cycle during system startup. 
A5  Almost Dirty Device Count  Total number of devices that have an almost dirty 
status (not necessarily a trouble). 
A6  Dirty Device Count  Total number of devices that are in Dirty Trouble. 
A7  Excessively Dirty Device Count  Total number of devices that are in Excessively 
Dirty Trouble. 
A8 Current Year   
A9 Current Month   
A10  Current Day of Month   
A11 Current Hour   
A12 Current Minute   
 
The user analog pseudo card in the 4010 is at Card Address 21.  It has 25 points 
available for specialized applications programming.  The analog user pseudos 
can have custom labels assigned to them. 
 
Continued on next page 
Pseudo Points, Continued 
Analog Pseudo Points 
4010 System Analog Pseudos 
4010 User Analog Pseudos 