6-3
 
This section describes how to Add an IDNet Point, Edit a TrueAlarm Point, and 
Delete a TrueAlarm Point.  
 
Use the following steps to Add an IDNet point to the 4010 FACP. 
 
1. Press <MENU>. 
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed 
and then press <ENTER>.  A warning appears, indicating that the 4010 is 
no longer in the Fire Alarm Operation mode. 
 
 
 
 
 
3. Press <ENTER> to continue. 
4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is 
displayed and then press <ENTER>. 
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until 
<TRUEALARM> is displayed and then press <ENTER>. 
6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Add 
IDNet Point> is displayed and then press Enter.   
7.  The first unused point in the system (for example, M1-1) is displayed.  Press 
<NEXT> or <PREVIOUS> to scroll through your list of unused points 
until the desired point is displayed and then press Enter. 
8.  Follow the prompts to confirm this action. 
 
Note:  If there are 250 devices present in the 4010 (maximum allowed), the 
system informs you that the IDNet channel is full and does not allow 
you to add any more points. 
 
Use the following steps to Edit a TrueAlarm point in the 4010 FACP. 
 
1. Press <MENU>. 
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed 
and then press <ENTER>.  A warning appears, indicating that the 4010 is 
no longer in the Fire Alarm Operation mode. 
 
 
 
 
 
3. Press <ENTER> to continue. 
4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is 
displayed and then press <ENTER>. 
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until 
<TRUEALARM> is displayed and then press <ENTER>. 
 
Continued on next page 
Configuring TrueAlarm Points 
Overview 
Add IDNet Point 
Edit TrueAlarm Point 
Pro
rammin
 
Please Wait . . .  
Fire Alarm Operation Suspended 
Please Wait . . .  
Fire Alarm Operation Suspended 