7-6
The Alarm Signal Cut-Out Timer allows you to set a duration for how long
signals sound after an alarm. In other words, when an alarm condition exists, the
signals sound until silenced. With this option set at two minutes, building
signals sound on alarm for two minutes and then automatically stop sounding.
However, the alarm condition does remain active in the panel. The default
setting for this option is No Cutout (meaning a manual Alarm Silence is required
to shut off signals).
Use the following steps to set the Alarm Signal Cut-Out timer on the 4010
FACP.
1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3. Press <ENTER> to continue.
4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<ALARM CUT-OUT TIMER> is displayed and then press <ENTER>.
6. Press <NEXT> or <PREVIOUS> to set the timer from 0-60 minutes and
then press Enter.
7. Follow the prompts to confirm this action.
Alarm Cut-Out Timer
Overview
Setting the Alarm Cut-Out
Timer
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
BrandSimplex
Model4010
CategoryFire Alarms
LanguageEnglish

Related product manuals