EasyManuals Logo

Simplex 4010 User Manual

Simplex 4010
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #120 background imageLoading...
Page #120 background image
8-16
OR & NOT
The OR Link operator links the current statement in Parallel with all previous
statements in an equation (see Figure 8-16).
[ ] [ ] [FIRE] [3-01]
[OR] [NOT] [FIRE] [3-02]
Figure 8-16
In Figure 8-16, if the condition of 3-01 is Fire OR the condition of 3-02 is NOT
Fire then the INPUT SIDE is true.
Another way to look at this equation is shown in Figure 8-17. In order to cross
from the INPUT SIDE of the equation to the OUTPUT SIDE, the first or the
second statement must be true.
Note: The NOT gate is shown as a normally closed contact. This
statement is true because there is a path from the Input to the
Output .
18-01
18-02
Figure 8-17
Field 3 contains the condition qualifier for the point listed in Field 4 (refer to
Table 8-1 for all INPUT SIDE condition qualifiers). Field 4 options change per
Condition Qualifier selected.
Continued on next page
Custom Control Programming, Continued
Field 2 (continued)
Fields 3 & 4
Field 1
Field 2 Field 3 Field 4
FIRST
STATEMENT
SECOND
STATEMENT
M1-01
M1-02
INPUT SIDE
(Statements 1 & 2)
OUTPUT SIDE
This statement is true because
M1-01 is not in the FIRE
condition and M1-02 is not in
the FIRE condition.
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing

Related product manuals