11-13
Table 11-3 lists the function options and their descriptions.
Table 11-3. Function Menu Options and Descriptions
Function Option Description
Manual Evacuation Activates the Manual Evacuation operation
(NACs activate and Fire Alarm LED flashes
until Ackd).
City Circuit Disconnect* Disconnects the City Circuit.
Control Point Bypass* Bypasses the following Control Points:
On until Silence signals
Resettable signals
AHU outputs
Elevator Bypass* Bypasses the Elevator Recall.
Doorholder Bypass* Bypasses Doorholder operation.
Lamp Test Illuminates all LEDs and all LCD segments on
the display.
Earth Fault Latch Latches intermittent Earth Fault Troubles into
the 4010.
User Defined Key 1 One of two user-defined function keys.
User Defined Key 2 One of two user-defined function keys.
Display Current Time Displays current time during abnormal
conditions.
*Activation of these options causes a trouble at the FACP.
User Control Functions, Continued
Using the Function Options
(continued)
Operation